The Y-Bus Matrix

The bus admittance matrix (Y-bus) is the fundamental data structure of power flow analysis. It encodes the entire network topology and parameters in a single sparse matrix that relates bus voltages to bus currents:

$$\mathbf{I} = \mathbf{Y} \cdot \mathbf{V}$$

Every power flow solver builds the Y-bus as its first step.


Why a Matrix?

Consider a simple 3-bus network:

     Bus 1 ───────── Bus 2
       │               │
       │               │
       └───── Bus 3 ───┘

At each bus, Kirchhoff's Current Law says: current injected = sum of currents flowing out on branches.

We could write this as three separate equations, but it's much cleaner as a matrix equation:

$$\begin{pmatrix} I_1 \ I_2 \ I_3 \end{pmatrix} = \mathbf{Y} \cdot \begin{pmatrix} V_1 \ V_2 \ V_3 \end{pmatrix}$$

The Y-bus matrix $\mathbf{Y}$ captures all branch admittances and how buses connect.


Building the Y-Bus

For a network with $n$ buses, the Y-bus is an $n \times n$ complex matrix built from branch admittances.

Off-Diagonal Elements

For $i \neq j$, the element $Y_{ij}$ equals the negative of the admittance connecting buses $i$ and $j$:

$$Y_{ij} = -y_{ij}$$

If buses $i$ and $j$ are not directly connected, $Y_{ij} = 0$.

Why negative? Current flowing from bus $i$ to bus $j$ is:

$$I_{i \to j} = y_{ij}(V_i - V_j)$$

This contributes $+y_{ij}V_i$ to bus $i$'s current (leaving) and $-y_{ij}V_i$ to bus $j$'s current equation. The negative sign in $Y_{ij}$ captures this relationship.

Diagonal Elements

The diagonal element $Y_{ii}$ equals the sum of all admittances connected to bus $i$:

$$Y_{ii} = \sum_{j \neq i} y_{ij} + y_i^{\text{shunt}}$$

This includes:

  • Series admittances of all branches connected to bus $i$
  • Shunt admittances at bus $i$ (capacitors, reactors, line charging)

The Admittance of a Branch

For a branch with impedance $\mathbf{Z} = R + jX$:

$$y = \frac{1}{\mathbf{Z}} = \frac{1}{R + jX} = \frac{R - jX}{R^2 + X^2}$$

In power systems notation, we write $y = g + jb$ where:

  • $g = \frac{R}{R^2 + X^2}$ (series conductance)
  • $b = \frac{-X}{R^2 + X^2}$ (series susceptance)

Example: Building a 3-Bus Y-Bus

Consider this network:

       y₁₂ = 0.5 - j2.0
  [1] ────────────────── [2]
   │                      │
   │ y₁₃ = 0.3 - j1.5     │ y₂₃ = 0.4 - j1.8
   │                      │
  [3] ────────────────────┘

(All values in per-unit. No shunts for simplicity.)

Off-diagonal elements:

$$Y_{12} = Y_{21} = -y_{12} = -(0.5 - j2.0) = -0.5 + j2.0$$

$$Y_{13} = Y_{31} = -y_{13} = -(0.3 - j1.5) = -0.3 + j1.5$$

$$Y_{23} = Y_{32} = -y_{23} = -(0.4 - j1.8) = -0.4 + j1.8$$

Diagonal elements:

$$Y_{11} = y_{12} + y_{13} = (0.5 - j2.0) + (0.3 - j1.5) = 0.8 - j3.5$$

$$Y_{22} = y_{12} + y_{23} = (0.5 - j2.0) + (0.4 - j1.8) = 0.9 - j3.8$$

$$Y_{33} = y_{13} + y_{23} = (0.3 - j1.5) + (0.4 - j1.8) = 0.7 - j3.3$$

Full Y-bus:

$$\mathbf{Y} = \begin{pmatrix} 0.8 - j3.5 & -0.5 + j2.0 & -0.3 + j1.5 \ -0.5 + j2.0 & 0.9 - j3.8 & -0.4 + j1.8 \ -0.3 + j1.5 & -0.4 + j1.8 & 0.7 - j3.3 \end{pmatrix}$$

Notice:

  • Symmetric (for networks without phase shifters)
  • Diagonal elements have negative imaginary parts (typical transmission lines are inductive)
  • Each row sums to zero if there are no shunts (current conservation)

The π-Model and Line Charging

Real transmission lines have distributed capacitance to ground, modeled as shunt elements at each end (the π-model):

         y_series
    ──┬───/\/\/───┬──
      │           │
    jB/2        jB/2
      │           │
     ─┴─         ─┴─

This adds $jB/2$ to the diagonal elements at each end:

$$Y_{ii} \mathrel{+}= jB_{ik}/2 \quad \text{(for each branch } ik \text{ connected to bus } i)$$

Line charging is significant for long high-voltage lines and causes lightly-loaded lines to generate reactive power.


Transformers in the Y-Bus

Transformers with tap ratio $t$ require special treatment. For a transformer between buses $i$ and $j$ with:

  • Series admittance $y$
  • Tap ratio $t$ (typically near 1.0)

The Y-bus contributions are asymmetric:

$$Y_{ii} \mathrel{+}= \frac{y}{t^2}$$

$$Y_{jj} \mathrel{+}= y$$

$$Y_{ij} = Y_{ji} = -\frac{y}{t}$$

Physical interpretation: The tap ratio changes the effective impedance seen from each side. Off-nominal taps (t ≠ 1) make the Y-bus asymmetric.

Phase Shifters

Phase-shifting transformers add a complex tap ratio $t \angle \phi$:

$$Y_{ij} = -\frac{y}{t e^{-j\phi}}, \quad Y_{ji} = -\frac{y}{t e^{j\phi}}$$

This creates asymmetry: $Y_{ij} \neq Y_{ji}$, enabling active power flow control.


Y-Bus Properties

Sparsity

Real power networks are sparse — each bus connects to only a few others. The Y-bus inherits this sparsity:

  • A 1000-bus network might have 1,500 branches
  • Y-bus has 1,000,000 elements, but only ~3,000 are non-zero

GAT stores Y-bus in sparse format (CSR/CSC), making operations efficient.

Symmetry

For networks with only transmission lines and transformers (no phase shifters):

  • $Y_{ij} = Y_{ji}$ — the matrix is symmetric
  • This allows efficient storage and computation

Phase shifters break symmetry.

Row Sums

For a network without shunts, each row of Y-bus sums to zero:

$$\sum_{j} Y_{ij} = 0$$

With shunts, row sums equal the total shunt admittance at that bus.

Singularity

The Y-bus is singular (determinant = 0) for any connected network. This reflects the fact that we can add any constant to all voltages without changing currents — there's no absolute voltage reference.

Power flow handles this by fixing the slack bus angle.


From Y-Bus to Power Flow

The power flow equations come from combining $\mathbf{I} = \mathbf{Y} \cdot \mathbf{V}$ with the complex power relationship $S = V \cdot I^*$:

$$S_i = V_i \cdot I_i^* = V_i \sum_{k=1}^{n} Y_{ik}^* V_k^*$$

Separating into real and imaginary parts:

$$P_i = \sum_{k=1}^{n} |V_i||V_k|(G_{ik}\cos\theta_{ik} + B_{ik}\sin\theta_{ik})$$

$$Q_i = \sum_{k=1}^{n} |V_i||V_k|(G_{ik}\sin\theta_{ik} - B_{ik}\cos\theta_{ik})$$

where:

  • $Y_{ik} = G_{ik} + jB_{ik}$
  • $\theta_{ik} = \theta_i - \theta_k$

These are the nonlinear equations solved by Newton-Raphson.


Z-Bus: The Inverse

The bus impedance matrix is $\mathbf{Z} = \mathbf{Y}^{-1}$. Unlike the sparse Y-bus, Z-bus is fully dense.

Z-bus is used for:

  • Fault analysis: $I_{\text{fault}} = V / Z_{kk}$ for a fault at bus $k$
  • Sensitivity analysis: How voltage at bus $i$ changes with injection at bus $j$

Because Z-bus is dense, it's rarely computed for large networks. Instead, we solve $\mathbf{Y} \cdot \mathbf{x} = \mathbf{b}$ directly using sparse LU factorization.


Building Y-Bus in GAT

GAT builds the Y-bus in the ybus.rs module:

let ybus = build_ybus(&buses, &branches);

This:

  1. Creates a sparse matrix structure
  2. Iterates through branches, adding series and shunt elements
  3. Handles transformer tap ratios
  4. Returns a sparse complex matrix ready for power flow

You can inspect the Y-bus with gat inspect --ybus.


Key Takeaways

  1. Y-bus encodes the network: $\mathbf{I} = \mathbf{Y} \cdot \mathbf{V}$
  2. Off-diagonal: $Y_{ij} = -y_{ij}$ (negative branch admittance)
  3. Diagonal: $Y_{ii} = \sum y_{ij} + \text{shunts}$ (sum of connected admittances)
  4. Sparse and symmetric for typical networks (phase shifters break symmetry)
  5. Foundation for power flow, fault analysis, and sensitivity studies